SADER IMPORT & EXPORT LTD.
OPzV Battery PDF Print E-mail
 
 

EverExceed tubular plate OPzV Range gelled, maintenance free sealed valve regulated lead acid rechargeable batteries offer their superior performance and reliability in both controlled and harsh uncontrolled environments. EverExceed state-of-the-art manufacturing facilities with wealthy experience ensure it's tubular OPzV gelled batteries reliable performance, safety, outstanding battery life and value. Each cell is 100% factory tested. EverExceed tubular OPzV batteries can be used in float or deep cycle (1500 x 80%)service and have a design life of 20 years at 20°C. EverExceed tubular OPzV batteries can be stored up to 2 years at 20°C without fresh charging.

 
Catalogue Download
Specification
● Positive electrode: Tubular Plate with     antiminy-free special alloy
● Negative electrode: Flat Grid plate
● Electrolyte: Suspended Thixotropic Gel
● Container & Cover SAN Optional V-0
● Separator: Microporous plastic
● Float Voltage: 2.23 VPC +/- 1% at 20 C
   Max. Charge Voltage: 2.40 VPC at 20 C
● Safety Valve: 1-3 PSI Self-Resealing
● Terminals: Integral Copper Insert
● Interconnects: Insulated cables

 
20 years design life
Tubular plate
Single cell
Nominal capacity:
200 - 3000Ah
 
 
deep discharge recovery
Maintenance free
Recycleable
Valve regulated lead-acid
 
 
General Specifications
Model No.
C10 Ah 1.80
C5 Ah 1.75
C3 Ah 1.75
C1 Ah 1.70
Ri (1) m W
lk (2) A
Outline Dimensions (mm/inch)

Approx.

Weight (kg)

Lenght
Width
Height(h2)
Height(h1)
2V 4 OPzV 200
210
179
158
117
0.94 2235 103 206 380 354 20
2V 5 OPzV 250
260
223
197
145
0.78 2710 124 206 380 354 24
2V 6 OPzV 300
310
268
236
174
0.60 3420 145 206 380 354 29
2V 5 OPzV 350
370
331
285
212
0.61 3450 124 206 496 470 31
2V 6 OPzV 420
450
397
342
255
0.49 4220 145 206 496 470 36
2V 7 OPzV 490
520
463
399
297
0.51 4100 166 206 496 470 42
2V 6 OPzV 600
630
555
492
369
0.44 4750 145 206 671 645 50
2V 9 OPzV 630
660
585
516
387
0.42 4850 254 210 496 470 54
2V 7 OPzV 700
730
645
573
431
0.38 5500 254 210 496 470 60
2V 11 OPzV 770
810
705
630
473
0.35 6300 254 210 496 470 66
2V 8 OPzV 800
820
740
654
491
0.30 6820 191 210 671 645 68
2V 10 OPzV 1000
1030
925
819
614
0.25 8200 233 210 671 645 82
2V 12 OPzV 1200
1230
1110
984
738
0.21 9850 275 210 671 645 97
2V 12 OPzV 1500
1550
1430
1269
920
0.19 10500 275 210 795 821 120
2V 16 OPzV 2000
2070
1905
1713
1226
0.15 14000 399 212 797 772 160
2V 20 OPzV 2500
2580
2385
1986
1533
0.12 17500 478 212 797 772 200
2V 24 OPzV 3000
3090
2855
2571
1840
0.10 21000 576 212 797 772 240
(1),(2)internal resistance and short - circuit - current from IEC 896-1
   
4 OPzV 100 up to 6 OPzV 600
6 OPzV 2000
20 OPzV 2500 up to 24 OPzV 3000
   
Design
positive electrode tubular - plate with a woven polyester gauntlet and solid grids in a corrosion- resistant PbCaSn - alloy
negative electrode grid - plate in a PbCaSn alloy with long - life expander material 
separation microporous separator
elektrolyte sulphuric acid with a density of 1,24 kg/l, fixed as GEL by fumed silica
container high impact, halogen-free SAN (Styrol-Acryl-Nitril), grey coloured, UL rating 94HB
lid high impact, halogen-free SAN (Styrol-Acryl-Nitril), grey coloured, UL rating 94HB
valve valve with flame arrestor
opening pressure approx. 100 mbar,
closing pressure approx. 50 mbar
pole - bushing 100% gas- and electrolyte-tight, sliding-pole
kind of pole M10 brass insertion
connectors flexible insulated copper cables, with cross-section of
35, 50, 70 or 95 mm²
kind of protection IP 25 regarding DIN 40050, touch protected according VBG 4
Charging
IU - characteristic Imax without limitation
U = 2,23 to 2,25V/cell +- 1%, between 10°C and 45°C
D U/D T = -0,004 V/K below 10°C in the monthly average
boost charge U = 2,35 to 2,40V/cell, time limited
charging time up to 90% 6h with 1,5*I10 initial current, 2.23 V/cell, 50% C10 discharged
Discharge characteristics
reference temperature 20°C
initial capacity 100%
depth of discharge (DOD) normally up to 80%
deep discharges  more than 80% DOD or discharges beyond final discharge
voltages (dependent on discharge current) have to be avoided
Maintenance
every 6 months  check battery voltage, pilot cell voltage, temperature
every 12 months  record battery and cell voltages and temperatures
Operational data
operational life > 15 years at 20°C
>7,5 years at 30°C
>4 years at 40°C
maintenance-free no topping-up water during operational life
IEC 896-2 cykles 1200
self-discharge app. 2% per month at 20°C
recovery after deep discharge very good
operational temperature -20°C to 45°C
recommended 10°C to 30°C
short-time 45°C to55°C
ventilation requirement 25% (f1=0,5 x f2=0,5)due to VDE 0510 part 2
standard DIN 40 742 part 1
tests according IEC 896-2,
safety standard VDE 0510, part 2
transport no dangerous goods during air-, sea- and land transport